Case study · Commercial electrical · SW4

Hot water thermostat and fused spur replacement at a Clapham venue.

Hot water cylinder not regulating at a Clapham venue. Existing fused spurs faulty, cabling identified as undersized for the load. Spurs replaced, cabling upgraded, new thermostat fitted. Full electrical testing throughout.

SectorRetail venue with kitchen
Postcode areaSW4 (Clapham)
KitHot water cylinder · fused spur supply
FaultFaulty thermostat · faulty fused spurs · undersized cabling
StandardsBS 7671 · NICEIC-aligned
Engineer of recordStewat Rogers

The brief

Existing customer in SW4 Clapham reported the hot water cylinder no longer regulating: water arriving cold at the taps despite the cylinder showing as energised. Return visit with parts to replace the thermostat and review the supply.

On site

Attended with required parts, liaised with the manager at head office, collected keys to access the premises.

Safe isolation

Isolated the electrical supply to the affected unit at the consumer unit. Carried out safe isolation procedures per BS 7671 (locked off, tested, retested) before removing any cover or making any electrical connection live or dead.

Fused spur replacement

Stripped out the faulty fused spurs feeding the hot water cylinder circuit. Identified the existing power supply cabling as undersized for the load the cylinder draws: the cable rating was below the manufacturer-spec current for the heater element, which had been a contributing factor to the fused spur degradation.

Upgraded the cabling to meet current load requirements and BS 7671 safety standards. New fused spurs supplied and fitted, correctly rated for the cylinder draw.

Thermostat replacement

Supplied and fitted a new thermostat to the hot water cylinder. Connected per manufacturer wiring diagram. Reinstated power to the circuit.

Test

Carried out full testing of the system: insulation resistance, earth continuity, polarity per BS 7671. Verified thermostat regulating correctly across its operating range by monitoring water temperature pull-up under load.

All components now operating correctly and safely. Test results recorded and certificate issued.

Outcome

Cost band

Return visit including thermostat replacement, fused spur swap and cabling upgrade typically £280-£480 + VAT depending on cable run length and certificate scope. Parts charged at trade rates.

Hot water, heating or commercial electrical fault?

Same in-house team handles electrical, gas and refrigeration sides. BS 7671 testing and certification on every install.

More on commercial electrics →

Commercial electrical work?

NICEIC-aligned to BS 7671. EICRs, plant-room wiring, catering equipment electrical, hot water and cylinder work. London + south east.

📞 Call 020 7871 3006 · 24/7 WhatsApp